Analog Output Baseplate
Current Output: 4–20 mA
Voltage Output: Optional 0–10 V DC
Typically ±0.1% of full scale
Current Output: 750 Ω (4–20 mA)
Voltage Output: ≥ 1 kΩ (0–10 V)
Operating Temperature:
-40°C to +70°C (-40°F to +158°F)
INPUT MODULE / ANALOG
Points:32, commoned
Nominal input current:4–20 mA DC
Operational current range:2–22 mA DC
Absolute maximum field voltage:33 V DC
Absolute maximum input current:50 mA DC
Input bandwidth (3dB):16 Hz
Source impedance:180 Ω
Resolution:12 bits
Absolute error:0.15% of full scale (20 mA)
Diagnostic:Force-to-value diagnostic (FVD)
Scan time:<1 ms for all 32 points
Main Processor Baseplate
Input Voltage: 24 VDC nominal
Speed: High-speed TMR
Operating Temperature:
-40°C to +70°C (-40°F to +158°F)
Digital Input Baseplate
Fault current130 mA,
typical200 mA, maximum
Voltage Range: Typically 24 V DC
High (ON): 15–30 V DC
Low (OFF): 0–5 V DC
Channel-to-channel isolation: ≥ 1500 V AC/DC
Typical: < 10 ms
Digital Output Baseplate
Voltage Range: 24 V DC
Max Continuous Current: 2 A per channel
Inrush Current: Supports up to 5 A for 100 ms
Channel-to-channel isolation: ≥ 1500 V AC/DC
Turn-On Delay: < 1 ms
Operating Temperature:
-40°C to +70°C (-40°F to +158°F)
Current input Terminal Board
Operating temperature: -40°C to +85°C for operation in harsh environments.
Power supply: 24 VDC for compatibility with standard industrial power supplies.
I/O configuration:
Analog input: 8 to 32 points for versatile signal acquisition from sensors.
Analog output: 4 to 16 points for precise control of process variables.
Logic I/O: 32 to 128 points for comprehensive process monitoring and control