Digital Input Module
Number of inputs 16-channel, module isolation
Input signa:
No-voltage contact
ON: 1 kΩ maximum
OFF: 100 kΩ minimum
Input current 6 mA ± 20 %
Contact rating 24 V DC +20 % / -10 %
Input response time 40 ms maximum
Power Supply Module
Nominal Input Voltage: 100-240 VAC
Input Voltage Range: 90-264 VAC
Frequency: 50/60 Hz
Nominal Output Voltage: 48 VDC
Voltage Regulation: ±1%
Maximum Output Current: 13 A
Digital Output Module
Number of outputs 8-channel, module isolation
Output voltage 24 V DC
Output voltage drop 1 V maximum
External power supply rating 24 V DC, 5 A minimum
Maximum leak current at output offstatus 1.6 mA
Output format Current source
Maximum load current 0.6 A/output line
Minimum load current 35 mA
Load resistance range 40 to 685 Ω
Output response time 30 ms maximum
Analog Output Module
Output signal 4 to 20 mA
Allowable load resistance 0 to 750 Ω
Circuit-open detection Less than 0.65 mA
Accuracy ±48 µA
Data update period 10 ms
Drift due to ambient temperature change ±16 µA/10 ˚C
Analog Output Module
4 to 20 mA
16 isolated
standard switch-overresponse
in redundant configuration
1500 V AC, for 1 minute
0 to 750 Ω
Less than 0.65 mA
±48 µA
±16 µA/10 ˚C
230 mA (5 V DC)
540 mA (24 V DC)