Digital Output Module
Points:16, commoned
Nominal output voltage:24 V DC
Operational voltage range:15–30 V DC
Absolute maximum output voltage:33 V DC
Absolute maximum reverse input voltage:–0.6 V DC
Leakage to load (Off-state):<1 mA
On-state voltage drop:<1 V DC @ 1.5 A
Loop-back scan time:<1 ms for all 16 points